Min.Order : PCS
Quantity:
-
+
Total Cost :
Product Details
Packing Information
Pcs/Carton: N/A
Packing Size/Carton:N/A
Packing Vol/Carton: N/A
N.W./Carton: N/A
G.W./Carton: N/A
QTY in 40HQ: N/A
QTY in 40GP: N/A
QTY in 20GP: N/A
Product Description
Product Series
Model
C1K/1KS
C2K/2KS
C3K/3KS
Rated Power
VA/W
1kVA / 0.8kW
2kVA / 1.6kW
3kVA / 2.4kW
Input
Nominal Voltage
220VAC
Voltage Range
115 ~ 300VAC
Frequency Range
46~54Hz(default), user adjustable within 40~60Hz
Power Factor
0.97
Connection
IEC320-10A inlet
IEC320-16A inlet
Output
Voltage
220VAC ± 2%
Frequency
46~54Hz or 50Hz ± 0.2Hz (Line mode) 50Hz ± 0.2Hz ( Battery mode)
Waveform
Sine Wave
Distortion
3%
4%
Overload Capability
108%~150% for 30 sec., ³150% for 300 ms
Current Crest Ratio
3:1
Connections
IEC320 * 4
IEC320 * 6
IEC320 * 3 and Terminal Block
Battery
Type
Sealed, Maintenance free, Lead-Acid
Quantity
12V7AH*3
12V7AH*6
Back-up Time (Full load)
5 min
9 min
Recharge Time
8 hrs to 90% of capacity after full load discharge
Bypass
Automatic Transfer
on overload and UPS failure
Before UPS Power-on
Default “NO”, user adjustable to “YES”
80~264VAC (Default), user adjustable within 80~286VAC
Transfer Time
0 ms; less than 4 ms from inverter to bypass and vice versa
LED Indicators
Status
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault
Audible Alarm
Bypass, On battery mode, Battery low, Overload, Fault
Acoustic Noise
At 1 meter distance
45 dBA
50 dBA
Communications
DB-9 Port
RS-232 Serial Interface
Intelligent Slot
Options: Web Power, AS400 Card or Win Power CMC
Network Surge Protection
RJ45 I/O port available for network or Fax/Modem
Environmental
Operating Temperature
0 ~ 40°C
Operating Humidity
20 ~ 90% non-condensing
Weight
Net (Kg)
13/6.5
31.5/10.5
32/12
Dimensions
W x D x H (mm)
360 x 145 x 225
192 x 460 x 348
C1K/2K/3K batteries inside; C1KS/2KS/3KS without batteries